Documentation |
|
|
|
| Features |
Zero
stacking
High power density
CE mark on selected models
650
microsecond transient response time
Built in OVP
with front panel adjust
Built in
thermal protection
CC/CV with auto crossover
Soft Start
Series or
parallel, master-slave operation
Common
programming with, TCR, EMHP and ESS
True zero
voltage and current adjustability
|
Other Solutions |
|
Lower Power |
Gen2U |
|
Higher Power |
ESS |
|
|
|
|
EMS - 2kW*, 2.5kW*, 5kW, up to 600A
EMS 2kW and 2.5kW models will be
discontinued late in 2008 - click here for info
|
 |
The EMS series are high
power switch mode AC to DC power supplies for applications where high
efficiency, precise regulation and a high degree of packing density
and light weight are required.
This
series of high frequency switching power supplies is
designed to operate as a source of constant current/constant
voltage with automatic crossover. All EMS Power Supplies
are fully programmable via an analog programming or (optional)
RSTL digital interface, allowing for systems integration
to meet your specific requirements.
The EMS series represents an important
element in our broad line of switching power supplies.
Beginning in 1969 with multiple patents awarded, Lambda Americas has continued to invest in the development and
engineering of the EMS series. Successful applications
include semiconductor processing, medical, scientific and
research laboratories. The EMS series offers the best of
customer tested and application proven features, while
incorporating the latest advancements in technology for
the user of power conversion systems.
|
Specification
|
AC Input
2 kW models: 220 VAC single phase (standard)
2.5 kW models: 220 VAC single phase and 208 VAC three phase (user
selectable)
5 kW models: 208 VAC three phase, 400VAC three phase (CE)
All models 50/60 Hz
Softstart AC inrush
Consult factory for other inputs
Output
Characteristics
Regulation: 0.1%
Stability: 0.05%
Transient response: 650 microseconds for 30% load change
(models up to 20 VDC)
Operating temperature: 0-50 Deg C full output, derate
above 50 Deg C.
Protection Features
Overvoltage (up to 300 VDC outputs)
Overtemperature
Overcurrent
|
Programming
Front panel controls and remote analog
resistance,
voltage and current programming (standard);
0-5 V and 0-10 V (optional) Internal RS232
and IEEE-488 (optional)
Embedded IEEE/RS232 available as option on 1kW models in 1U high
chassis.
Mechanical
Size:
2/2.5kW - 19" W x 3 1/2" H x
22" D
5kW - 19" W x 5 1/4" H x
22" D
Weight:
0.6kW - 15lbs/7kg
1kW - 17lbs/7kg
2kW - 30lbs/13kg
2.5kW - 35lbs/16kg
5kW - 60lbs/27kg
Outline Drawings(PDF):
EMS 2kW Standard
EMS 2.5kW Standard
EMS 5kW 208VAC 3PH
EMS 5kW 380VAC 3PH
EMS 5kW CE (Low Voltage)
EMS 5kW CE (Hi Voltage)
|
Standard Model Listing
|
| Model Number |
Rated Power
(Watts)
|
Output
Voltage
(Volts)
|
Output
Current
(Amps)
|
Output Ripple
(mV) p-p Carrier
|
EMS 7.5-250
EMS 7.5-300
EMS 7.5-600 |
2000
2500
5000
|
0-7-5
0-7-5
0-7-5
|
0-250
0-300
0-600
|
75
75
75
|
EMS 10-200
EMS 10-250
EMS 10-500 |
2000
2500
5000
|
0-10
0-10
0-10
|
0-200
0-250
0-500
|
75
75
75
|
EMS 20-100
EMS 20-125
EMS 20-250 |
2000
2500
5000
|
0-20
0-20
0-20
|
0-100
0-125
0-250
|
75
75
75
|
EMS 30-65
EMS 30-80
EMS 30-165 |
2000
2500
5000
|
0-30
0-30
0-30
|
0-65
0-80
0-165
|
75
75
75
|
EMS 40-50
EMS 40-60
EMS 40-125 |
2000
2500
5000
|
0-40
0-40
0-40
|
0-50
0-60
0-125
|
75
75
75
|
EMS 60-33
EMS 60-40
EMS 60-80 |
2000
2500
5000
|
0-60
0-60
0-60
|
0-33
0-40
0-80
|
75
75
75
|
EMS 80-25
EMS 80-30
EMS 80-60 |
2000
2500
5000
|
0-80
0-80
0-80
|
0-25
0-30
0-60
|
100
100
100
|
EMS 100-20
EMS 100-25
EMS 100-50 |
2000
2500
5000
|
0-100
0-100
0-100
|
0-20
0-25
0-50
|
100
100
100
|
EMS 150-13
EMS 150-16
EMS 150-33 |
2000
2500
5000
|
0-150
0-150
0-150
|
0-13
0-16
0-33
|
120
120
120
|
EMS 300-6
EMS 300-8
EMS 300-16 |
2000
2500
5000
|
0-300
0-300
0-300
|
0-6
0-8
0-16
|
150
150
150
|
EMS 600-3.3
EMS 600-4
EMS 600-8 |
2000
2500
5000
|
0-600
0-600
0-600
|
0-3.3
0-4
0-8
|
250
250
250
|
|
Ordering Information
| EMS |
100 |
- |
20 |
- |
x |
- |
xx-xx |
- |
xxxx |
| Model |
Voltage |
|
Current |
|
AC Input |
|
Options |
|
Special Programming |
|